← Back to Home

Revision Volt

Electrical Formulas

A clear formula guide for electrical revision. Each formula shows what the symbols mean, when to use it and a quick worked example so learners understand the method instead of just memorising it.

12

key formulas

Ω

resistance, Zs and PFC

Vd

voltage drop made simple

BS 7671

useful for exam revision

Formula 01

Power Triangle

Formula

P = V × I | S² = P² + Q² | pf = P ÷ S

What the values mean

  • P = real power in watts (W) or kilowatts (kW)
  • V = voltage in volts (V)
  • I = current in amps (A)
  • S = apparent power in volt-amperes (VA) or kilovolt-amperes (kVA)
  • Q = reactive power in VAr or kVAr
  • pf = power factor

Used for

Used when calculating real power, apparent power, reactive power or power factor.

Quick example

A 230 V load draws 10 A. P = 230 × 10 = 2300 W, or 2.3 kW.

Revision tip

Remember: watts are the useful power doing the work.

Formula 02

Ohm’s Law Triangle

🔺

Formula

V = I × R | I = V ÷ R | R = V ÷ I

What the values mean

  • V = voltage in volts (V)
  • I = current in amps (A)
  • R = resistance in ohms (Ω)

Used for

Used to calculate voltage, current or resistance when two values are known.

Quick example

A 230 V load has a resistance of 46 Ω. I = 230 ÷ 46 = 5 A.

Revision tip

Cover the value you want in the triangle to see the formula.

Formula 03

Voltage Drop Formula

📉

Formula

Vd = (mV/A/m × Ib × L) ÷ 1000

What the values mean

  • Vd = voltage drop in volts (V)
  • mV/A/m = voltage drop value from cable tables
  • Ib = design current in amps (A)
  • L = route length of the circuit in metres (m)
  • 1000 = converts millivolts to volts

Used for

Used to calculate how much voltage is lost along a cable run.

Quick example

A 40 A circuit is 25 m long with a cable factor of 11 mV/A/m. Vd = 11 × 40 × 25 ÷ 1000 = 11 V.

Revision tip

Longer cable, higher current or higher mV/A/m all increase voltage drop.

Formula 04

Voltage Drop Percentage

Formula

%Vd = (Vd ÷ Vsupply) × 100

What the values mean

  • %Vd = voltage drop as a percentage
  • Vd = calculated voltage drop in volts (V)
  • Vsupply = nominal supply voltage, usually 230 V or 400 V

Used for

Used to check whether the voltage drop is within the permitted percentage.

Quick example

A 9.8 V drop on a 230 V circuit gives 9.8 ÷ 230 × 100 = 4.26%.

Revision tip

Lighting circuits usually have a lower permitted voltage drop than other final circuits.

Formula 05

PFC / PEFC / PSCC

💥

Formula

Ipf = V ÷ Z

What the values mean

  • Ipf = prospective fault current in amps (A) or kiloamps (kA)
  • V = voltage in volts (V)
  • Z = impedance in ohms (Ω)
  • PEFC = prospective earth fault current
  • PSCC = prospective short-circuit current
  • PFC = highest value between PEFC and PSCC

Used for

Used to check the maximum fault current that could flow and whether protective devices have enough breaking capacity.

Quick example

230 V with Ze of 0.18 Ω gives Ipf = 230 ÷ 0.18 = 1277.7 A, or 1.28 kA.

Revision tip

Record the highest measured value between PEFC and PSCC.

Formula 06

Zs Formula

🧲

Formula

Zs = Ze + (R1 + R2)

What the values mean

  • Zs = total earth fault loop impedance in ohms (Ω)
  • Ze = external earth fault loop impedance in ohms (Ω)
  • R1 = resistance of the line conductor
  • R2 = resistance of the circuit protective conductor (CPC)
  • R1 + R2 = resistance of the circuit line and CPC path

Used for

Used to calculate or verify earth fault loop impedance for a final circuit.

Quick example

Ze = 0.28 Ω and R1 + R2 = 0.37 Ω. Zs = 0.28 + 0.37 = 0.65 Ω.

Revision tip

Zs must be low enough to allow the protective device to disconnect in time.

Formula 07

Ib Design Current

🧠

Formula

Ib = P ÷ V

What the values mean

  • Ib = design current in amps (A)
  • P = power of the load in watts (W)
  • V = supply voltage in volts (V)

Used for

Used to calculate the current a circuit is expected to carry before selecting protective devices and cables.

Quick example

A 9.2 kW cooker on 230 V gives Ib = 9200 ÷ 230 = 40 A.

Revision tip

Convert kW to W before calculating. 9.2 kW = 9200 W.

Formula 08

Energy kWh Formula

£

Formula

Energy (kWh) = Power (kW) × Time (h)

What the values mean

  • Energy = electricity used in kilowatt-hours (kWh)
  • Power = load power in kilowatts (kW)
  • Time = running time in hours (h)
  • Cost = kWh × tariff

Used for

Used to work out energy use and running cost of electrical appliances.

Quick example

A 2 kW heater runs for 3.5 h. Energy = 2 × 3.5 = 7 kWh. At £0.28/kWh, cost = £1.96.

Revision tip

Minutes must be converted into hours before using the formula.

Formula 09

Three-Phase Current Formula

🔌

Formula

I = P ÷ (√3 × VL × pf)

What the values mean

  • I = line current in amps (A)
  • P = three-phase power in watts (W)
  • √3 = 1.732
  • VL = line voltage, usually 400 V
  • pf = power factor

Used for

Used to calculate the line current of a balanced three-phase load.

Quick example

An 18 kW motor at 400 V and pf 0.86 gives I = 18000 ÷ (1.732 × 400 × 0.86) = 30.2 A.

Revision tip

Use 400 V for UK three-phase line voltage unless the question states otherwise.

Formula 10

Correction Factor Formula

🧮

Formula

It = In ÷ (Ca × Cg × Ci × ...)

What the values mean

  • It = required tabulated current-carrying capacity of the cable
  • In = rating of the protective device in amps (A)
  • Ca = ambient temperature correction factor
  • Cg = grouping correction factor
  • Ci = thermal insulation correction factor
  • Other factors may apply depending on the installation method

Used for

Used when choosing a cable size after correction factors have reduced its current-carrying capacity.

Quick example

A 32 A device with Ca 0.87 and Cg 0.80 gives It = 32 ÷ (0.87 × 0.80) = 46 A.

Revision tip

Correction factors usually mean you need a larger cable, not a smaller one.

Formula 11

Ring Final R1 + R2

🔁

Formula

R1 + R2 ≈ (r1 + r2) ÷ 4

What the values mean

  • R1 + R2 = expected resistance at socket outlets
  • r1 = end-to-end resistance of the line conductor
  • r2 = end-to-end resistance of the CPC
  • ÷ 4 = approximate relationship used for a ring final circuit

Used for

Used during continuity testing of ring final circuits to estimate the expected R1 + R2 value.

Quick example

If r1 = 0.64 Ω and r2 = 1.04 Ω, R1 + R2 ≈ (0.64 + 1.04) ÷ 4 = 0.42 Ω.

Revision tip

This is for ring final circuits, not normal radial circuits.

Formula 12

Adiabatic Equation

🟩

Formula

S = √(I² × t) ÷ k

What the values mean

  • S = minimum protective conductor size in mm²
  • I = fault current in amps (A)
  • t = disconnection time in seconds (s)
  • k = factor based on conductor material, insulation and temperature limits

Used for

Used to check whether a CPC is large enough to withstand fault current until the protective device disconnects.

Quick example

I = 1000 A, t = 0.1 s and k = 115. S = √(1000² × 0.1) ÷ 115 = 2.75 mm².

Revision tip

Higher fault current or longer disconnection time increases the required CPC size.